Non-Flexible Cable Core Colors
Determination of non-flexible cable cores and bare conductors in fixed equipment.
Function | Rubber or p.v.c. Determining the colors of the tubing or disc inserted into the insulated, non-flexible cable core or bare conductor or cable core |
Grounding | Yellow-and-green or green * |
Single-phase a.c. circuit live end | Red (or yellow or blue * *) |
Single-phase or 3-phase a.c. circuit neutral end | Black |
3-phase a.c. circuit R-phase | Red |
3-phase a.c. circuit Y-phase | Yellow |
3-phase a.c. circuit B-phase | Blue |
2nd wire d.c. circuit positive end | Red |
2nd wire d.c. circuit negative end | Black |
Obtained from 3-wire system 2-wire d.c. circuit (positive or negative outer conductor | Red |
3rd tel d.c. circuit positive end | Red |
3rd tel d.c. circuit middle end | Black |
3rd tel d.c. circuit negative end | Blue |
5-core armored p.v.c. fifth of the cable (special purpose) vessel | Orange |
*Until 31.12.1977, only green color is allowed to be used for the grounding conductor; after that, the use of this color does not comply with the requirements of the article.
**If desired in large equipment, up to the last distribution box, red can be used as an option.