LV Type Ground Type Transformers Calculation of Output Cables

Grid power transformer generalDetailed information about the calculation of LV output cables of ground type transformers can be found in the table below. You can find it.

Cable Cross Section Single Cable Current Carrying Capacity (A) Parallel 2 Cable Current Carrying Capacity (A) Parallel 3 Cable Current Carrying Capacity (A) Parallel 4 Cable Current Carrying Capacity (A)
1x300 mm² Cu.PVC/PVC 660 1056 1366 1637
1x400 mm² Cu.PVC/PVC 800 1280 1656 1984
1x500 mm² Cu.PVC/PVC 910 1456 1884 2257
1x630 mm² Cu.PVC/PVC 1040 1664 2153 2579
Transformer Power Transformer Output Current Possible Suitable Sections Optimal Section (Smallest total copper section)
315kVA 438 All 1x300
500kVA 695 2x300,1x400,1x500,1x630 1x400
800kVA 1112 3x300,2x400,2x500,2x630 2x400
1000kVA 1390 4x300,3x400,2x500,2x630 2x500
1250kVA 1738 4x400,3x500,3x630 3x500
1500kVA 2085 4x500,3x630 3x630
1600kVA 2226 4x500,4x630 4x500
2000kVA 2782 6x500,5x630 5x630
2500kVA 3478 8x500,8x630 8x500